Inspection
Inspection Details
Equipment ID
11252
11252
Inspection Date
3/1/2021
3/1/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
add8a77b-45eb-49fc-abb7-b27f105ea82c
add8a77b-45eb-49fc-abb7-b27f105ea82c
Location
Vintage Gardens
3310 N WOODBINE RD, SAINT JOSEPH, MO
Phone: (816) 279-0774
3310 N WOODBINE RD, SAINT JOSEPH, MO
Phone: (816) 279-0774
Owner
Attn: Vintage Gardens
Vintage Gardens
3310 N WOODBINE RD, SAINT JOSEPH, MO 64505
Phone: (816) 279-3330 Ext: 10
Email: dmcgary@capitalseniorliving.net
Vintage Gardens
3310 N WOODBINE RD, SAINT JOSEPH, MO 64505
Phone: (816) 279-3330 Ext: 10
Email: dmcgary@capitalseniorliving.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Fire service hat lens on car operating panel has been knocked out and is missing. | 8/19/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need to identify unmarked floor lockout keyswitch located on car operating panel. | 8/26/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Elevator machine room door needs to be self locking. | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door unlocking rollers are missing on 1st and 2nd floor hoistway doors. | 8/19/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need to identify floor lockout keyswitch on car operating panel to corresponding car call that it locks out. | 8/26/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door needs to be non-defeatable and self locking. | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Replace missing hoistway door unlocking rollers on first and second floor. | 3/1/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No documentation of maintenance or testing in on site maintenance record log. | 7/15/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(c)(5) | No | No | Written checkout procedure for overspeed valve not on site. Needs to be kept in machine room. | 7/15/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 7/15/2022 |
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 212 | No | No | INSTALL LOCK NUTS ON DEAD END OF CABLES IN HOISTWAY OVERHEAD | 7/16/2025 |