Inspection
Inspection Details
Equipment ID
7417
7417
Inspection Date
3/2/2021
3/2/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
92589061-c330-4850-8986-91092440bd45
92589061-c330-4850-8986-91092440bd45
Location
Sheraton Hotel
7730 Bonhomme Ave, Clayton, MO
Phone: (314) 863-0400
7730 Bonhomme Ave, Clayton, MO
Phone: (314) 863-0400
Owner
Attn: Aimbridge Hospitality
Aimbridge Hospitality
5851 Legacy Circle, Suite 400, Plano, TX 75024
Phone: (314) 863-0400
Email: Licensing@aimhosp.com
Aimbridge Hospitality
5851 Legacy Circle, Suite 400, Plano, TX 75024
Phone: (314) 863-0400
Email: Licensing@aimhosp.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 3/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance records on site. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance records on site. | 4/14/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Test incomplete. Car top still needs to be inspected. | 10/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance control program in the machine room | 4/14/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned of water and debris | 4/14/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Perform the required emergency power testing | 4/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair or replace lower roller guide assembly | 4/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 2.22 | Yes | No | Install required buffer switches on the gas charged car buffer | 4/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 2.22 | Yes | No | Install required buffer switch on the counterweight gas charged buffer | 4/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Install missing buffer switches on car and counterweight gas charged Oleo buffers | 1/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Repair bent lower right guide roller mount and roller | 1/8/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.26.8 | Yes | No | Emergency brake release handle failed to drift car. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car door restrictor shall work. Failed to stop door motion. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | No | No | Governor rope shall be shortened/replaced to allow proper tension device clearance. | 1/8/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed. Apply rust prevention treatment to all pit steel, investigate/repair water leak. | 1/8/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP shall be provided. Fire service testing must be documented monthly and repair, PM, callback logs are missing | 1/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn counterweight lower guide roller. | 1/8/2026 |