Inspection
Inspection Details
Equipment ID
5890
5890
Inspection Date
3/3/2021
3/3/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
UNK
UNK
Governor Rope Pull
100/600
100/600
Door Closing Force
27/19
27/19
External ID
d8ee84d3-5404-4510-b07f-4c43502d7c80
d8ee84d3-5404-4510-b07f-4c43502d7c80
Location
The Westin Hotel-St. Louis
811 Spruce St, St. Louis, MO
Phone: (314) 621-2000
811 Spruce St, St. Louis, MO
Phone: (314) 621-2000
Owner
Attn: The Westin St. Louis
HEI St. Louis LLC
811 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (314) 552-5810
Email: Tom.dietz@westinstlouishotel.com
HEI St. Louis LLC
811 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (314) 552-5810
Email: Tom.dietz@westinstlouishotel.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete. Need to test car and counterweight buffers, safeties, 125% brake test, and fire service. | 4/15/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/15/2021 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor does not work. | 4/15/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/29/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 6/2/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not work. Re-inspection required | 3/13/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 9/3/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required | 9/3/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 2/4/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 6/6/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two-way communication inoperable and shall be repaired, or replaced. | 7/29/2025 |