Inspection
Inspection Details
Equipment ID
18315
18315
Inspection Date
3/3/2021
3/3/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
6
6
Governor Rope Pull
280/950
280/950
Door Closing Force
18
18
External ID
636b2a87-0b6e-4901-8785-76be13d980fe
636b2a87-0b6e-4901-8785-76be13d980fe
Location
Dickmann Building
3115 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 932-1159
3115 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 932-1159
Owner
GST Properties LLC
3115 S GRAND BLVD STE 300, SAINT LOUIS, MO 63118-1046
3115 S GRAND BLVD STE 300, SAINT LOUIS, MO 63118-1046
Billing
Attn: GST Properties LLC
3115 S GRAND BLVD STE 300, SAINT LOUIS, MO 63118-1046
3115 S GRAND BLVD STE 300, SAINT LOUIS, MO 63118-1046
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Governor and safeties shall be tested. | 5/22/2020 | |
conversion | conversion | n/a | Need copy of current state operating certificate in machine room. | 6/13/2023 | ||
conversion | conversion | n/a | Door closing force exceeds 30 lbs. | 6/13/2023 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/13/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Remove all material, including 4 cinder blacks from the car top. | 6/13/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | Install a cover on the door operator. | 6/13/2023 | ||
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | Install a suspension rope and governor rope data tag. | 6/13/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | Remove unsupported wiring from the overhead. | 6/13/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)13 | The holes in the overhead shall be sealed with approved solid material. | 6/13/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | The open electrical box with exposed wiring in the hoistway at the 4th floor shall be covered. | 6/13/2023 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | The material not necessary for the operation of the elevator, trash, and defective parts shall be removed from the machine room. | 6/13/2023 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | The covers shall be installed on all electrical equipment in the machine room, including the controllers. | 6/13/2023 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | The machines shall be numbered. | 6/13/2023 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | A monthly fire service testing log shall be posted and kept on-site. | 6/13/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A maintenance control program (MCP) shall be provided. | 6/13/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | An up to date, legible copy of the schematics shall be located in the machine room for each elevator. | 6/13/2023 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | Wiring running from controller 1 to controller 2 shall be enclosed in raceway or wireway. | 6/13/2023 | ||
MO Minimum : Elevators | (J) - Counterweights | (J)2 | Suspension ropes on counterweight shackles shall have all cotter pins installed. | 6/13/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | Traveling cables shall be properly supported and run in wireway or raceway 6' past the point of suspension in the hoistway. | 6/13/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | A current ABC type fire extinguisher shall be located in the machine room. | 6/13/2023 | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | The safeties pulled out 60" for the annual test. The drum operated safety rope shall pull out a maximum of 42" before the safeties contact the rail | 3/3/2021 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | The car top shall be kept clean. Clean the car top. | 6/13/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The in car emergency bell shall be operational. | 3/28/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The in car emergency lighting shall be operational. | 3/28/2024 |