Inspection
Inspection Details
Equipment ID
8696
8696
Inspection Date
2/10/2021
2/10/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
3da9f1ee-6795-492c-a70d-a186e8b09403
3da9f1ee-6795-492c-a70d-a186e8b09403
Location
Tri County Medical Bldg
4800 MEXICO RD, SAINT PETERS, MO
Phone: (636) 397-1634
4800 MEXICO RD, SAINT PETERS, MO
Phone: (636) 397-1634
Owner
Attn: Donna Lamparter
McKelvey Properties
17280 N Outer 40 Rd, Ste 201, Chesterfield, MO 63005
Phone: (636) 778-3246
Alt Phone: (636) 669-9111
Email: DonnaL@mckelveyproperties.com
McKelvey Properties
17280 N Outer 40 Rd, Ste 201, Chesterfield, MO 63005
Phone: (636) 778-3246
Alt Phone: (636) 669-9111
Email: DonnaL@mckelveyproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 12/15/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/15/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 12/15/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/9/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The emergency lowering device (ERU) shall be operational. | 12/9/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in section 620-51 shall be provided with an auxiliary contact that positively opened mechanically and opening shall not be solely dependent on springs. This contact shall cause the additional power source to be connected from its load when the disconnecting means is in the open position. | 12/9/2022 |
| A17.1-1996 : Elevators | 2.37 Pressure switch | 306.14 Pressure switch | Yes | No | A pressure switch shall be provided in the line between the cylinder and the valve which shall be activated by the loss of positive pressure at the top of the cylinder. | 12/9/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 12/15/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 12/9/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no up-to-date operating certificate in the machine room. | 10/20/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. | 5/20/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Battery lowering shall work. | 4/29/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certi?cate is required in machine room. | 4/29/2026 |