Inspection
Inspection Details
Equipment ID
11168
11168
Inspection Date
2/17/2021
2/17/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Timothy Roberts
Timothy Roberts
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
0fd362c9-755a-4606-b5ee-0874ec3a977d
0fd362c9-755a-4606-b5ee-0874ec3a977d
Location
Pierre Laclede Center
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
Owner
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: d_kasten@commonwealth.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: d_kasten@commonwealth.com
Billing
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: dkasten@commonwealthcommercial.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: dkasten@commonwealthcommercial.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | All machine room lighting shall be operational. | 10/1/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Replace the hoist ropes. | 4/23/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Schedule a full lad test of the emergency power system on elevators 1-8. | 4/23/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The emergency power shall be tested with 125% of capacity. | 7/28/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency/standby power operation of the elevators shall be operational. | 10/5/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When testing fire service, the fire service key switch would not go onto "hold". Repair or replace the switch as needed. | 4/7/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/21/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. The monthly fire service checklist is missing. | 3/21/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When testing fire service, the fire service key switch would not go onto "hold". Repair or replace the switch as needed. | 5/12/2022 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. | 6/26/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Phase 2 switch Halo to be replaced. It is currently unreadable. | 3/21/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. | 3/21/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete: Began annual & Cat 5 testing, remaining testing to be finished by another inspector. Items tested - Hoistway, door, gate, restrictor, cartop, pits, light, bell, phone, comp-sheave, ring & string, terminal limits. | 3/13/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. It dials out, but no answer. | 3/13/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. Bell is very weak. | 3/13/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired State operating certificate in the machine room. |