Inspection
Inspection Details
Equipment ID
14507
14507
Inspection Date
3/18/2021
3/18/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Ryan Bollinger
Ryan Bollinger
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
F-25 R-24
F-25 R-24
External ID
2a43b748-7f9b-4b0f-8b48-0f8df2a6f859
2a43b748-7f9b-4b0f-8b48-0f8df2a6f859
Location
Nevada Regional Medical Center
800 S ASH ST, NEVADA, MO
Phone: (417) 667-3355
800 S ASH ST, NEVADA, MO
Phone: (417) 667-3355
Owner
Attn: Chad Boswell
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: cboswell@nrmchealth.com
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: cboswell@nrmchealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | needs record of oil loss | 2/21/2020 |
| conversion | conversion | n/a | No | No | needs maintance records on site | 2/21/2020 |
| conversion | conversion | n/a | No | No | pit shall be clean and dry-removal of any oil on floor | 2/21/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | I-1 Mo -min--oil and debree in pit--pit needs to be cleaned | 2/21/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | current certificate needs to be displayed | 2/21/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit needs to be cleaned--water/oil/debree | 3/23/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Oil Accumulation in pit | 1/11/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | No records | 1/11/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must provide cat 5 test on or before next Annual insp. 8.6.5.16.5 | 1/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current operating Cert. in Mach room 5.100(2) | 1/11/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Phone Operable. 8.6.4.15 | 9/18/2025 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Must repair/replace jacke Packing gland to limit oil loss. (pit overflow bucket was full and had been emptied in the last 30 days.) 8.6.5.5 | 5/29/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit must be kept free of oil. 8.6.4.7 | 5/29/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency phone operable. 8.6.4.15 |