Inspection
Inspection Details
Equipment ID
2614
2614
Inspection Date
7/31/2017
7/31/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
Location
Division of Workforce Development
215 East 5th St, Sedalia, MO
Phone: (660) 530-5627
215 East 5th St, Sedalia, MO
Phone: (660) 530-5627
Owner
Division of Workforce Development
215 East 5th St, Sedalia, MO 65301
215 East 5th St, Sedalia, MO 65301
Billing
Attn: OA/Facilities Mgt.
301 E High St., , MO 65102
301 E High St., , MO 65102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump pump hole needs cover | 3/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-closing and self-locking | 3/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Bldg phone line. | 11/18/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door closer broken. | 3/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump hole needs cover. | 3/31/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cartop inspection station won't run up. | 3/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | water seeping in pit from wall corner needs to be sealed to maintain dry pit | 3/14/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | openings at top back corners of shaft large enough for birds to enter. 2 dead birds on cartop.. openings need to be sealed to prevent from reoccurring | 3/14/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Top of hoistway still has an opening for birds to enter. 2 have been closed. | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs location information | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top needs cleaning | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | em phone has wrong location address, | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | cartop needs cleaning. oil and p[arts | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | need sump cover |