Inspection
Inspection Details
Equipment ID
13616
13616
Inspection Date
3/19/2021
3/19/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Ryan Williams
Ryan Williams
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
51af9021-c704-414a-9033-a43360d73153
51af9021-c704-414a-9033-a43360d73153
Location
Convent Gardens
4497 Pershing Ave, St. Louis, MO
Phone: (314) 243-6126
4497 Pershing Ave, St. Louis, MO
Phone: (314) 243-6126
Owner
Attn: The Lipton Group
The Lipton Group
9100 Overland Plz, St. Louis, MO 63114
Phone: (000) 000-0000
The Lipton Group
9100 Overland Plz, St. Louis, MO 63114
Phone: (000) 000-0000
Billing
Attn: Property Manager
Convent Gardens
4497 Pershing Ave, Apt 107, St. Louis, MO 63108
Phone: (314) 535-1618
Email: cvtpropmgr@liptongroup.com
Convent Gardens
4497 Pershing Ave, Apt 107, St. Louis, MO 63108
Phone: (314) 535-1618
Email: cvtpropmgr@liptongroup.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Car top emergency exit shall be constructed of material to withstand 150#, fastened from top of elevator. | 8/14/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | All hoistway wiring shall be enclosed in metal conduit or flexible conduit. | 8/14/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | No | No | The 3rd floor and basement floor electrical interlock needs to be adjusted. | 8/14/2019 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)5 | No | No | Provide car platform guard | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current state operating certificate needs to be properly displayed in machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergencylight in car shall work | 8/29/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)9 | No | No | Provide a phase reversal device on controller | |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Brake failed 125% lower and hold test. Red Tagged | 8/29/2024 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Provide NO PASSENGERS signage in car with 1/2" or larger lettering | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing rope guard on governor | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace missing cover on cartop electrical box for car lighting | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform full load, full speed testing of car safeties | 8/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | Yes | 8.6.4.20.10 Elevator will not lift rated capacity. Red Tagged | 8/29/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. It is currently lying on the floor, it shall be mounted as required. | 9/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | The data on the door operator tag shall be filled out. | 9/3/2024 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of Section 8.7. | 9/3/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | A duplex GFCI receptacle shall be provided in the machine room. | 9/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. | 9/3/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | The machine room shall be provided with permanent lighting providing a minimum illumination of 200 lx (19 fc) at the floor level. | 9/3/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | All machine room wiring shall be enclosed. | 9/3/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | The wireway covers shall be installed in the hoistway. | 9/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | The hall buttons, fire service phase one key-switch, and phone monitor have not been permanently installed. Before the elevator can be released for operation, these items must be permanently installed and a re-inspection must be performed. | 9/3/2024 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | Yes | No | 2.11.11.6 - The tabs on the hall door gibs must be turned down into the sill slot. | 9/3/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. It is currently lying on the floor, it shall be mounted as required. | 11/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | The data on the door operator tag shall be filled out. | 11/26/2024 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of Section 8.7. | 11/26/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | A duplex GFCI receptacle shall be provided in the machine room. | 11/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. | 11/26/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | The machine room shall be provided with permanent lighting providing a minimum illumination of 200 lx (19 fc) at the floor level. | 11/26/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | All machine room wiring shall be enclosed. | 11/26/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | The wireway covers shall be installed in the hoistway. | 11/26/2024 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | Yes | No | 2.11.11.6 - The tabs on the hall door gibs must be turned down into the sill slot. | 11/26/2024 |