Inspection
Inspection Details
Equipment ID
9684
9684
Inspection Date
6/8/2018
6/8/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
29f506c6-fa92-436a-8582-85a40bd65037
29f506c6-fa92-436a-8582-85a40bd65037
Location
Appletree Square
15801 MANCHESTER RD, ELLISVILLE, MO
15801 MANCHESTER RD, ELLISVILLE, MO
Owner
Baywood Realty
8922 MANCHESTER RD, SAINT LOUIS, MO 63144-2622
8922 MANCHESTER RD, SAINT LOUIS, MO 63144-2622
Billing
Attn: Baywood Realty
8922 MANCHESTER RD, SAINT LOUIS, MO 63144-2622
8922 MANCHESTER RD, SAINT LOUIS, MO 63144-2622
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lights shall work. | 11/21/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency lighting shall work. | 11/21/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 4/20/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | NEC - Sump pump shall be on independent circuit separate from light switch. | 5/29/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/29/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be kept free of excess debris/dirt/lint. | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept dry. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak |