Inspection
Inspection Details
Equipment ID
17474
17474
Inspection Date
4/1/2021
4/1/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
3
3
Governor Rope Pull
50/200
50/200
Door Closing Force
16
16
External ID
fa153309-13be-436f-9efb-2461e3a91b35
fa153309-13be-436f-9efb-2461e3a91b35
Location
Cupples Station Apartments
1023 Spruce St, St. Louis, MO
Phone: (314) 241-1225
1023 Spruce St, St. Louis, MO
Phone: (314) 241-1225
Owner
Attn: Cupples Station Loft, LLC
Cupples Station Loft, LLC
1023 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Cupples Station Loft, LLC
1023 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Billing
Attn: Cupples Station Apartments
Cupples Station Loft, LLC
1023 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: ann.rito@hriproperties.com
Cupples Station Loft, LLC
1023 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: ann.rito@hriproperties.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 5/1/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide Cat 5 testing of emergency generator and selector switch (fire control room). | 8/17/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 7/7/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit shall be kept clean. | 7/7/2022 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | Car top GFCI has open neutral, repair as needed. | 7/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean car top. | 7/7/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP | 7/7/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide testing | 7/7/2022 |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1002.2g | No | No | Provide testing | 7/7/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency Power was not transferred to the elevator during testing | 7/7/2022 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 202 | No | No | Need to change all worn roller guides | 7/18/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/18/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. No Answer | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics, on-site(as well as fault code lists and parameter tables) | |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 201 | No | No | Need to change worn/damaged lower counterweight roller guides. | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 210.13 | No | No | Replace missing/damaged/faded "Do not use elevator in case of fire" Signage on multiple floors | |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. |