MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
3/12/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency/standby power shall be tested. Note: The unit has an indicator light and key-switch for emergency power. Building personnel were unsure if this unit is served by a generator in the case of a grid failure. If it is, it shall be tested. If it isn't, the related fixture shall be removed.
|
3/15/2023
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/12/2026
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
When the hall fire recall key-switch is in the "ON" position, or an initiation device has been activated, a stopped car shall have the in-car stop switch rendered inoperative as soon as the car moves away from the landing. A moving car shall have the switch rendered inoperative without delay. Note: The acceptance tests were witnessed by St. Louis County last month. The code data plate is marked for compliance with A17.1-2013, as required by St. Louis County. A17.1-2013 requires the switch to be rendered inoperative. A17.1-2016 (the current MO State code) does not.
|
3/15/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection)
|
Yes
|
No
|
When the hall fire recall key-switch is in the "ON" position, or an initiation device has been activated, a stopped car shall have the in-car stop switch rendered inoperative as soon as the car moves away from the landing. A moving car shall have the switch rendered inoperative without delay. Note: The acceptance tests were witnessed by St. Louis County last month. The code data plate is marked for compliance with A17.1-2013, as required by St. Louis County. A17.1-2013 requires the switch to be rendered inoperative. A17.1-2016 (the current MO State code) does not. This violation was originally cited in 2022 and has not been addressed. Customer to apply for a variance from the State of Missouri to clear violation.
|
5/28/2024
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it.
|
3/12/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The emergency/standby power shall be tested.
|
3/24/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency power operation shall be tested.
|
3/12/2026
|