Inspection
Inspection Details
Equipment ID
16344
16344
Inspection Date
4/2/2021
4/2/2021
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
External ID
f93727a4-ea20-40f8-b81f-fd36993f66ed
f93727a4-ea20-40f8-b81f-fd36993f66ed
Location
Bed Bath & Beyond
8340 EAGER RD, SAINT LOUIS, MO
Phone: (314) 727-9300 Ext: 101
8340 EAGER RD, SAINT LOUIS, MO
Phone: (314) 727-9300 Ext: 101
Owner
Attn: Facilities Department
BBBY # 219
650 Liberty Ave, Union, NJ 07083
Phone: (908) 855-4639
Email: Craig.Rohner@bedbath.com
BBBY # 219
650 Liberty Ave, Union, NJ 07083
Phone: (908) 855-4639
Email: Craig.Rohner@bedbath.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 2/5/2019 |
| A17.1-1996 : Elevators | 5.5 - Traveling cables | 102.2 | Yes | No | Traveling cable outer jacket is split. Repair traveling cable. | 2/5/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | Yes | Phone in elevator cab does not work. | 11/19/2019 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV installed and not sealed. Perform OSV test on or before next annual inspection. | 4/26/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 4/26/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | Has’21 docs, needs ‘22 docs. | 3/6/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 3/6/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperative. Re-inspection required | 11/25/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher is expired, needs serviced or replaced | 3/6/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Extension cord coming through wall has to be removed and hole sealed shut to maintain fire rating. | 1/12/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State operating certificate shall be posted in the machine room in a non-combustible frame with a clear portective plate over it. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Class "ABC" fire extinguisher shall be provided in the elevator electrical machime rooms. |