Inspection
Inspection Details
Equipment ID
16883
16883
Inspection Date
4/2/2021
4/2/2021
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
370 - OSV
370 - OSV
Slide
Governor Rope Pull
Door Closing Force
External ID
36d6950f-438d-48e7-9430-cba6fd9761ba
36d6950f-438d-48e7-9430-cba6fd9761ba
Location
Bed Bath & Beyond
8340 EAGER RD, SAINT LOUIS, MO
Phone: (314) 727-9300 Ext: 101
8340 EAGER RD, SAINT LOUIS, MO
Phone: (314) 727-9300 Ext: 101
Owner
Attn: Facilities Department
BBBY # 219
650 Liberty Ave, Union, NJ 07083
Phone: (908) 855-4639
Email: Craig.Rohner@bedbath.com
BBBY # 219
650 Liberty Ave, Union, NJ 07083
Phone: (908) 855-4639
Email: Craig.Rohner@bedbath.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 2/5/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | On initial phase I, fire recall at the alternate level, the door open button does not work. Repair | 2/5/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | Yes | Phone in elevator cab does not work. | 11/19/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 4/26/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV installed and not sealed. Perform OSV test on or before next annual inspection. | 4/26/2022 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | No | No | Hoistway door closer missing, repair as needed. BOTH FLOORS. | 4/19/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Update MCP. Has ‘21 docs, needs ‘22. | 4/19/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Phase II not working, repair as needed. 15 days to repair and reinspect. 3/1/22 | 4/28/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate has expired | 5/10/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperative. Re-inspection required | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher is expired, have serviced or replaced | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Elevator has been decommissioned. |