Inspection
Inspection Details
Equipment ID
3030
3030
Inspection Date
7/19/2018
7/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Jeffrey VanZant
Jeffrey VanZant
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
884a0eb2-f88b-4fac-9dad-3a1dbaea6d07
884a0eb2-f88b-4fac-9dad-3a1dbaea6d07
Location
RBAC
1000 W AUSTIN BLVD, NEVADA, MO
1000 W AUSTIN BLVD, NEVADA, MO
Owner
Cottey College
1000 W AUSTIN BLVD, NEVADA, MO 64772-2763
1000 W AUSTIN BLVD, NEVADA, MO 64772-2763
Billing
Attn: Cottey College
1000 W AUSTIN BLVD, NEVADA, MO 64772-2763
1000 W AUSTIN BLVD, NEVADA, MO 64772-2763
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. | 11/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Battery lowering device shall work with power loss. | 11/17/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase 2 shall work, "Hold" does not work. | 12/23/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1 : Alarm shall work with power loss. (REINSPECTION within 30 days) | 12/23/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase 2 shall work, "Hold" does not work. | 12/23/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1 : Alarm shall work with power loss. (REINSPECTION within 30 days) | 12/23/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase 2 switch not working properly. | 8/10/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | G/2.7.1/8.6.1.6.5: Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. 4lb installed, should be 5-10lbs ABC | 9/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | G(1).3.26.10 Battery Lowering shall work. Repair or replace. | 9/15/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide current state operating certificate | 8/14/2023 |