Inspection
Inspection Details
Equipment ID
5636
5636
Inspection Date
3/22/2021
3/22/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Timothy Mayes
Timothy Mayes
Relief Valve Pressure
Slide
12"
12"
Governor Rope Pull
80/740
80/740
Door Closing Force
NA
NA
External ID
08b0f3c1-57bd-4e5d-9cb4-a309261fb6d0
08b0f3c1-57bd-4e5d-9cb4-a309261fb6d0
Location
Bayer R&D
700 Chesterfield Pkwy W, Chesterfield, MO
Phone: (000) 000-0000
700 Chesterfield Pkwy W, Chesterfield, MO
Phone: (000) 000-0000
Owner
Attn: David Walter
Bayer Research and Development Services LLC
700 Chesterfield Pkwy W, Chesterfield, MO 63017
Phone: (314) 682-8665
Email: david.walter.ext@bayer.com
Bayer Research and Development Services LLC
700 Chesterfield Pkwy W, Chesterfield, MO 63017
Phone: (314) 682-8665
Email: david.walter.ext@bayer.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | New hoistway penetrations shall be sealed (at the top floor). | 6/21/2019 |
| conversion | conversion | n/a | No | No | Wiring not related to the elevator shall not be added to the hoistway (at the top floor). | 6/21/2019 |
| conversion | conversion | n/a | No | No | A 2nd heat detector is required withing 24" of the second fire sprinkler head in hoistway overhead. | 6/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 2.2.3 - Safety screen mesh shall be installed between two hoistways. Passenger hydraulic on backside of freight car shall have a divider. | 6/27/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 6/27/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Some of the machine room walls have been torn down and are missing. It's currently open and without a door. The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. | 1/21/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 1/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in-car emergency light shall be operational. | 1/21/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 6/27/2025 |
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | Yes | No | Counterwight is on springs when car reached top final limit. Runby must be a minimum of 6 inches". Suspension ropes must be shortenend. |