Inspection
Inspection Details
Equipment ID
10167
10167
Inspection Date
8/16/2017
8/16/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wendy Eiss
Wendy Eiss
Mechanic Name
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
Location
Lange Middle School
2201 Smiley Lane, Columbia, MO
Phone: (573) 886-2243
2201 Smiley Lane, Columbia, MO
Phone: (573) 886-2243
Owner
Columbia Public Schools
1818 W, worley Street, Columbia, MO 65203
1818 W, worley Street, Columbia, MO 65203
Billing
Attn: Columbia Public Schools
1818 W Worley Street, , MO 65203
1818 W Worley Street, , MO 65203
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Fire extinguisher in elevator machine room and mechanical room by elevator not inspected since 2014 | 9/30/2020 |
| conversion | conversion | n/a | No | No | Phase I fire service operation plaquered needed by key switch | 9/30/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone calls wrong # | 6/30/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump hole needs non combustible cover | 7/12/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency lowering batteries are bad. 2016 8.6.4.19.7 I believe but can't find mo min | 6/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher out of date | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs location information for contact | 7/20/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 12/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs correct contact | 7/11/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 12/21/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | STANDBY POWER MUST BE MADE OPERABLE | 7/30/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | STANDBY POWER MUST BE MADE OPERABLE |