Inspection
Inspection Details
Equipment ID
1873
1873
Inspection Date
4/6/2021
4/6/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
89d7b195-62f9-42b9-98d0-176f22ee1d3b
89d7b195-62f9-42b9-98d0-176f22ee1d3b
Location
Ameren Missouri
1901 Chouteau Ave, St. Louis, MO
Phone: (314) 363-4794
1901 Chouteau Ave, St. Louis, MO
Phone: (314) 363-4794
Owner
Attn: Ameren
Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency lights do not work. | 4/11/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/11/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The elevator safety drum rope was replaced at some point in time with a non-code conforming material. Safety drum rope must be of a corrosion-resistant non ferrous material and not be of tiller rope construction. Reinspection and safety test is required. | 5/13/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 5/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 1/25/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | The elevator safety drum rope was replaced at some point in time with a non-code conforming material. Safety drum rope must be of a corrosion-resistant non ferrous material and not be of tiller rope construction. Reinspection and safety test is required. | 1/25/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 5/13/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | The final limit switch in the pit shall be adjusted to activate before the buffer switch is activated. Currently the counterweight measurement is 5.5” and is activating before the normal directional and final limit switch activates. | 1/25/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Car safety mini drum cable wrong type material, replace. | 1/28/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/9/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Car door force exceeds 30#, adjust as needed. | 5/13/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The seismic detection operation of the elevator shall operate as designed. The elevator failed to recall to closest floor, open doors, and remain inoperable until reset by a licensed mechanic | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone shall establish 2-way communication on battery back up. | |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.1 | No | No | Minimum bottom clearance for counterweights shall measure no less than 6.5 inches. Measurements for this inspection proved 5 inches. Ropes shall be shortened. |