Inspection
Inspection Details
Equipment ID
14503
14503
Inspection Date
6/25/2018
6/25/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
3cb02187-26ea-4b6d-8c81-9fe69bc71106
3cb02187-26ea-4b6d-8c81-9fe69bc71106
Location
Lofts at 315
315 N 10TH ST, SAINT LOUIS, MO
315 N 10TH ST, SAINT LOUIS, MO
Owner
Killmanjaro IV
5501 PERSHING AVE, SAINT LOUIS, MO 63112-1703
5501 PERSHING AVE, SAINT LOUIS, MO 63112-1703
Billing
Attn: Asprient Properties LLC
5501 PERSHING AVE, SAINT LOUIS, MO 63112-1703
5501 PERSHING AVE, SAINT LOUIS, MO 63112-1703
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | Yes | Phone inoperative. Repair | 4/9/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 10/23/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher has not been serviced since 2014. | 7/1/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance control program. | 7/1/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 7/1/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Elevator pit light does not work. Repair or replace | 9/30/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher in machine room is dated 2014. Update fire extinguisher | 9/30/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator phone does not work on 110v emergency power or normal power. Repair or replace | 9/30/2022 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | Yes | No | Governor rope shall be replace due being submerged in water is rusted | 3/21/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Elevator pit light does not work. Repair or replace. | 4/1/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher in machin room is dated 2014. Update fire extinguisher. | 4/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Need to tag fire extinguisher in machine room to indicate the test date | 4/1/2024 |
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 212 | No | No | Need to install rope data tag on car shackle | 4/1/2024 |