Inspection
Inspection Details
Equipment ID
8520
8520
Inspection Date
6/26/2018
6/26/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
a13362d6-9316-408c-a0d2-286c4c62e70f
a13362d6-9316-408c-a0d2-286c4c62e70f
Location
Fifth Third Center
8000 MARYLAND AVE, CLAYTON, MO
8000 MARYLAND AVE, CLAYTON, MO
Owner
Hoffmann International Commercial Real Estate
8000 MARYLAND AVE, CLAYTON, MO 63105-3752
8000 MARYLAND AVE, CLAYTON, MO 63105-3752
Billing
Attn: 8000 Maryland LLC
8000 MARYLAND AVE STE 1120, CLAYTON, MO 63105-3919
8000 MARYLAND AVE STE 1120, CLAYTON, MO 63105-3919
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Perform brake, buffers, car & counterweight, safety slide test. | 8/1/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) | 7/30/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Red tag issued: damaged hoistway ropes. Replace ropes and check driver for damaged grooves. | 10/4/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested. | 10/4/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Top elevator exit shall be operable without the use of tools. Wing bolts are broken and shall be replaced. | 9/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Strain device is missing from traveling cable under car, needs to be installed. | 9/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP shall be current including fire service test log. | 9/15/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in machine room in non-combustible frame. | 9/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Emergency power operation must be tested. | 6/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Suspension ropes shall be shortened. | 9/1/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room floors, machinery and control spaces shall be kept free of water, dirt, rubbish, oil, and grease. | 9/1/2026 |