Inspection
Inspection Details
Equipment ID
1816
1816
Inspection Date
7/20/2018
7/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Brent Bonham
Brent Bonham
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
6ce1b149-a9a0-4f6e-b25b-ca26d33189ac
6ce1b149-a9a0-4f6e-b25b-ca26d33189ac
Location
Smithfield Farmland
22123 HIGHWAY 5, MILAN, MO
22123 HIGHWAY 5, MILAN, MO
Owner
Smithfield
11500 N AMBASSADOR DR, KANSAS CITY, MO 64153-1151
11500 N AMBASSADOR DR, KANSAS CITY, MO 64153-1151
Billing
Attn: Smithfield Farmland
22123 HIGHWAY 5, MILAN, MO 63556-2382
22123 HIGHWAY 5, MILAN, MO 63556-2382
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Top of car inspection station does not function. | 10/9/2018 |
| conversion | conversion | n/a | No | No | Repair pit light. Pit light not working and electrical wires are exposed. | 10/9/2018 |
| conversion | conversion | n/a | No | No | elevator phone does not function. | 10/9/2018 |
| conversion | conversion | n/a | No | No | Enclose wires from hoistway duct to first floor hall button fixture in metal conduit. | 10/9/2018 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Multicable wiring from hoistway duct to first floor hall button fixture needs to be in flexible metal conduit, not plastic tubing. | 10/9/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Need to install light switch that operates pit light. Switch should be accessible from the pit access door. | 10/9/2018 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)5 | No | No | Need to install car platform toe guard on elevator. | 11/23/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 1/6/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter instructions inside the elevator | 1/6/2021 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | CAR DOES NOT HAVE A CAPACITY / LOADING CLASS / AND ''NO PASSENGERS'' SIGNAGE | 5/5/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)6 | Yes | No | THE UPPER DIRECTIONAL SWITCH ARM HAS BEEN REMOVED MAKING THE SWITCH INOPERABLE | 4/9/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)6 | Yes | No | PHASE 1 FIRE SERVICE SWITCH DOES NOT WORK | 4/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not work, repair emergency phone | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in pit, maintain dry pit | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | First floor flex to hall button in the hoistway is broken and hanging on the wiring, repair flex | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top |