Inspection
Inspection Details
Equipment ID
10870
10870
Inspection Date
4/9/2021
4/9/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Kevin Drury
Kevin Drury
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
57947394-7376-4bdb-b3c2-56fd5b1d26a9
57947394-7376-4bdb-b3c2-56fd5b1d26a9
Location
St. Louis City Hall
1200 Market St, St. Louis, MO
Phone: (314) 622-4635
1200 Market St, St. Louis, MO
Phone: (314) 622-4635
Owner
Attn: David Cleveland
City of St. Louis
1200 Market St, RM 301, St. Louis, MO 63103
Phone: (314) 622-4635
Email: clevelandd@stlouis-mo.gov
City of St. Louis
1200 Market St, RM 301, St. Louis, MO 63103
Phone: (314) 622-4635
Email: clevelandd@stlouis-mo.gov
Billing
Attn: Rick Ernst
City of St. Louis
1200 Market St, RM 301, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
City of St. Louis
1200 Market St, RM 301, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace broken roller guide assembly. | 2/13/2019 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Make car door restrictor operational. | 3/29/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate in the elevator machine room. | 4/27/2020 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 1001.2(e)(2) | Yes | No | Provide code compliant minimum counterweight runby. | 5/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | The barrier in the overhead shall be restored so that no opening exists. | 4/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.20.2 | Yes | No | A suspension rope tag shall be installed. | 4/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.20.2 | Yes | No | A governor rope tag shall be installed. | 4/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | 2.27.3.2.1(c) - The smoke detector in the top of the hoistway shall only be used where sprinklers are installed. The smoke detector in the top of the hoistway shall be removed. | 4/9/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/6/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The voice works, but video/text "yes/no" buttons are not working properly. | 5/28/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/3/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen. | 5/21/2026 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | Yes | No | Rope gripper wear swtich indicates gripper needs to be replaced. Will not reset without assistance. | 5/21/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current operating certificate shall be displayed in the equipment room in a non0-combustible frame. | 5/21/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be properly documented monthly on log sheet located in the MCP. | 5/21/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Current operating certificate shall be displayed in the equipment room in a non0-combustible frame. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Yes | No | Fire service testing must be properly documented monthly on log sheet located in the MCP. |