Inspection
Inspection Details
Equipment ID
3987
3987
Inspection Date
4/6/2021
4/6/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
12
12
External ID
47fc0311-8e48-4592-bdd2-d2b537e07bdb
47fc0311-8e48-4592-bdd2-d2b537e07bdb
Location
Rec-Plex
5200 MEXICO RD, SAINT PETERS, MO
Phone: (636) 939-4411
5200 MEXICO RD, SAINT PETERS, MO
Phone: (636) 939-4411
Owner
Attn: Chris Rohne
City of St. Peters
1 Saint Peters Centre Blvd, St. Peters, MO 63376
Phone: (000) 000-0000
Email: crohne@stpetersmo.net
City of St. Peters
1 Saint Peters Centre Blvd, St. Peters, MO 63376
Phone: (000) 000-0000
Email: crohne@stpetersmo.net
Billing
Attn: Chris Rohne
City of St. Peters
PO Box 9, St. Peters, MO 63376
Phone: (000) 000-0000
Email: crohne@stpetersmo.net
City of St. Peters
PO Box 9, St. Peters, MO 63376
Phone: (000) 000-0000
Email: crohne@stpetersmo.net
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/18/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/7/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The auxiliary power lowering operation shall be functional. | 11/8/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/7/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | Yes | No | All sprinkler risers and returns shall be located outside the hoistway, machine room, and machinery spaces. There is a sprinkler riser in the hoistway feeding sprinklers at more than one floor. Take corrective action or apply for a variance. | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A periodic test record for all periodic tests containing the applicable code requirement(s) and date(s) performed, and the name of the person or firm performing the test, shall be installed to be readily visible and adjacent to or securely attached to the controller of each unit in the form of a metal tag. The mechanic performing the test did not have any test tags. | 11/7/2025 |
| A17.1-2016 : Elevators | 2.31 - Relief Valves | 8.6.5.9 | Yes | No | The relief valve setting shall be resealed if the relief valve setting is altered or if the seal is broken. | 12/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. The elevator had a major alteration a year ago and the disconnects appear to be new. They need to be properly marked with feeder locations. Also, the function needs to be marked "elevator main" for the main disconnect and "elevator lighting" for the lighting. | 11/7/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | The auxiliary power lowering operation shall be functional. | 12/16/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The two-way communication means shall provide on demand to authorized personnel, information that identifies the building location and elevator number. | 12/16/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | Water and oil shall not be allowed to accumulate on pit floor. Find and correct source of leaks. | 12/16/2025 |