Inspection
Inspection Details
Equipment ID
5423
5423
Inspection Date
4/12/2021
4/12/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
John Carpentier, Sr.
John Carpentier, Sr.
Relief Valve Pressure
Slide
4"
4"
Governor Rope Pull
80/450
80/450
Door Closing Force
24
24
External ID
0c6977f4-ddcf-47a5-b9b7-5acb05e17393
0c6977f4-ddcf-47a5-b9b7-5acb05e17393
Location
York House on Lindell
4931 Lindell Blvd, St. Louis, MO
Phone: (345) 109-0329
Alt Phone: (314) 583-8628
4931 Lindell Blvd, St. Louis, MO
Phone: (345) 109-0329
Alt Phone: (314) 583-8628
Owner
Attn: Koplar Properties
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Billing
Attn: Koplar Properties
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: kelly@koplar.com
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: kelly@koplar.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Shorten the hoist ropes. | 6/11/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.6 - Final and emergency terminal stopping devices | 8.11.2.1.3(h) | Yes | Yes | Shorten the hoist ropes to allow proper operation on upper final limit. | 6/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Test the rope gripper for proper operation with 125% capacity. | 6/15/2020 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/7/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | This elevator previously had the ability to operate on standby/emergency power. The generator has now been disconnected but may be re-connected at some point. So long as the elevator does not operate on standby/emergency power, the emergency power fixture at the egress floor for this car shall be removed or covered. If/when the elevators are re-connected to the emergency generator, the emergency power indicator jewel shall be re-installed and standby/emergency power operation of the elevators shall be tested. | 4/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing gibbs and fire tabs at basement and first floor. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit still. Investigate/repair water leak. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Pit sump cover to be reinstalled, and shall be substantially flush to pit floor. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove rust from pit equipment. repaire/replace as needed. Apply rust orevention treatment to all pit sill. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Pit sump cover shall be substantially flush to pit floor. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on site documentation shall be provided in the machine room. |