Inspection
Inspection Details
Equipment ID
18363
18363
Inspection Date
4/26/2021
4/26/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Zachary Thieme
Zachary Thieme
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
28/25
28/25
External ID
497f06ed-42f3-4596-bbca-d743a3858891
497f06ed-42f3-4596-bbca-d743a3858891
Location
Salvation Army- St. Louis
10740 PAGE AVE, SAINT LOUIS, MO
Phone: (314) 423-7770
10740 PAGE AVE, SAINT LOUIS, MO
Phone: (314) 423-7770
Owner
Attn: Salvation Army- St. Louis
Salvation Army- St. Louis
2900 WASHINGTON AVE, SAINT LOUIS, MO 63103
Phone: (000) 000-0000
Salvation Army- St. Louis
2900 WASHINGTON AVE, SAINT LOUIS, MO 63103
Phone: (000) 000-0000
Billing
Attn: Salvation Army- St. Louis
Salvation Army- St. Louis
2900 WASHINGTON AVE, SAINT LOUIS, MO 63103
Phone: (000) 000-0000
Email: tracy.douglas@usc.salvationarmy.org
Salvation Army- St. Louis
2900 WASHINGTON AVE, SAINT LOUIS, MO 63103
Phone: (000) 000-0000
Email: tracy.douglas@usc.salvationarmy.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | A key switch on the car operating panel in the car is pushed in resulting in a possible electrical hazard and shall be repaired. | 11/15/2025 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection is required. | 7/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired/replaced. Remove the recovery unit after the packing gland has been repaired/replaced and record the oil loss per A17.1 2016 - 8.6.5.5.7 | 11/15/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 11/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Seal hole in the car operating panel, potential life/limb hazard. | 11/15/2025 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV in the pit is unsealed, provide testing. | 4/19/2024 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Remove scavenger unit from the pit. | 11/15/2025 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Provide code compliant means of oil recovery in the pit (buckets) | 11/15/2025 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Remove scavenger oil lines going back to the tank. | 11/15/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean the pit. | 11/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide existing battery backup lowering unit to work correctly. | 4/19/2024 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace missing car handrails. | 11/15/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post Phase I instructions near f/f switch in the lobby. | 11/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide Phase I halo ring to be readable, worn. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Hole in COP, missing switch. Seal. Potential life/limb hazard. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | Remove scavenger unit from the pit. | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | Remove scavenger return line. | 6/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Post current State Elevator Certificate. | 6/5/2024 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV in the pit is unsealed. Provide testing. | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | Provide code compliant means to collect jack oil for each piston. | 6/5/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | Yes | No | Clean the pit | 6/5/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide existing battery backup lowering unit to work. | 6/5/2024 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | Yes | No | Replace missing car hand rails. | 6/5/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Post Phase I instructions. | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Key switch halo ring is worn and unreadable. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Door open function failed on Phase II. | 6/5/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Provide machine room door to be self locking (no button) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | 3rd floor electronic directional arrow missing cover, provide. | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | No | Phase I halo worn and unreadable, replace. | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | No | Post Phase I instructions. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Yes | No | Replace missing car hand rails. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Clean the pit. | |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Yes | No | Remove scavenger unit from pit. | |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Yes | No | Provide means to collect oil from each piston. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide existing battery backup lowering unit to work. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. |