Inspection
Inspection Details
Equipment ID
19476
19476
Inspection Date
6/22/2018
6/22/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Kenneth Gustavson
Kenneth Gustavson
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
e6b4e127-fa10-492a-a243-191c73776487
e6b4e127-fa10-492a-a243-191c73776487
Location
TCM Realty
1409 WASHINGTON AVE, SAINT LOUIS, MO
1409 WASHINGTON AVE, SAINT LOUIS, MO
Owner
TCM Realty III, LLC
14949 MANCHESTER RD, BALLWIN, MO 63011-4624
14949 MANCHESTER RD, BALLWIN, MO 63011-4624
Billing
Attn: TCM Realty
14949 MANCHESTER RD, BALLWIN, MO 63011-4624
14949 MANCHESTER RD, BALLWIN, MO 63011-4624
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Door open button still not working on initial recall in Phase 1. | 7/25/2018 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Door detector (light ray) shall not open the door in Phase 1. | 7/25/2018 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | The elevator failed the 125% brake test. Unit Red Tagged. | 2/24/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 9/7/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/7/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, have serviced or replaced | 3/17/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 3/17/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. Re-inspection required | 4/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car is not working. Re-inspection required | 4/29/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 3/17/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car requires protection, such as plastic tubes and end caps or solid ceiling panels to protect passengers in event of bulb breakage. | 3/17/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 3/17/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace ceiling panels or guard light bulbs. | 3/17/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current MO.State operating certificate in machine room, |