Inspection
Inspection Details
Equipment ID
7439
7439
Inspection Date
4/20/2021
4/20/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jeffrey Woods
Jeffrey Woods
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
20F/29R
20F/29R
External ID
171e2543-30d1-4345-8b9c-39fb185968f1
171e2543-30d1-4345-8b9c-39fb185968f1
Location
St. Louis Community College-Meramec Campus
11333 BIG BEND RD, KIRKWOOD, MO
Phone: (314) 984-7750
11333 BIG BEND RD, KIRKWOOD, MO
Phone: (314) 984-7750
Owner
Attn: St. Louis Community College
St. Louis Community College
3221 McKelvey Rd, Bridgeton, MO 63044
Phone: (314) 539-5878
Email: jduarte@stlcc.edu
St. Louis Community College
3221 McKelvey Rd, Bridgeton, MO 63044
Phone: (314) 539-5878
Email: jduarte@stlcc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/19/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | A legible copy of the up to date wiring diagrams shall be kept on site. | 6/19/2020 |
| A17.1-2016 : Elevators | 5.4 - Normal terminal stopping devices | 3.25.1 | No | No | The bottom normal terminal stopping device (down directional limit) shall be adjusted to stop the car before it rests on the car buffer. | 6/19/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 5/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. The diagrams in the machine room are incomplete. | 6/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 2.25.2 | Yes | No | The down directional limit shall stop the car before landing on the buffers. The elevator lands on the buffers several inches before actuating the down directional limit. | 1/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work. | 8/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. The diagrams in the machine room are incomplete. | 8/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER |