Inspection
Inspection Details
Equipment ID
12870
12870
Inspection Date
4/30/2021
4/30/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
22
22
External ID
1475b147-8888-45a1-9ede-cf39b768a452
1475b147-8888-45a1-9ede-cf39b768a452
Location
Merchandise Mart Apartments
1000 Washington Ave, St. Louis, MO
Phone: (314) 436-6800
1000 Washington Ave, St. Louis, MO
Phone: (314) 436-6800
Owner
Attn: Marshiana Shaw
Mermart LLC
911 Washington Ave, Ste 400, St. Louis, MO 63101
Phone: (314) 436-6800
Fax: (314) 436-8532
Email: mshaw@mandelgroup.com
Mermart LLC
911 Washington Ave, Ste 400, St. Louis, MO 63101
Phone: (314) 436-6800
Fax: (314) 436-8532
Email: mshaw@mandelgroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | Repair handrail inside of the car. | 8/10/2020 | ||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 11/7/2023 | ||
| A17.1-1996 : Elevators | 3.19 - Guide rails fastening and equipment | 1001.2(c)(25) | There is a top and guide roller on the elevator car top that has deteriorated and shall be replaced. | 11/7/2023 | ||
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | x | There is a top guide roller on the counterweight that has deteriorated and shall be replaced. | 7/29/2022 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The fireman service phase I key switch housing is damaged and shall be replaced. Reinspection required. | 7/29/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. | 11/7/2023 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency communication inoperable. Re-inspection required | 8/21/2023 | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | Remove non elevator related materials from machine room | 11/7/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Elevator pit needs to be cleaned | 11/7/2023 | ||
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | Provide a handrail on the wall between 31" & 33" off the floor | 11/7/2023 | ||
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | Cover square hole in the car operating panel | 11/7/2023 | ||
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | Cover Square Hole in the car operating panel | 11/7/2023 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | x | Provide testing of the elevator on emergency power. | ||
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1002.2g | x | Provide testing of the elevator emergency power selector switch ( located in the Fire Command Room). |