Inspection
Inspection Details
Equipment ID
2184
2184
Inspection Date
6/6/2018
6/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Alfred Davis
Alfred Davis
Mechanic Name
Christopher Wiseman
Christopher Wiseman
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
10e2c07c-12a8-47e6-9189-b69449967636
10e2c07c-12a8-47e6-9189-b69449967636
Location
Wyndham at the Meadows
300 WILLOW BND, BRANSON, MO
300 WILLOW BND, BRANSON, MO
Owner
Wyndham Properties
201 WILLOW BND, BRANSON, MO 65616
201 WILLOW BND, BRANSON, MO 65616
Billing
Attn: Meadows 1 & 11 POA
110 WILLOW BND, BRANSON, MO 65616-3462
110 WILLOW BND, BRANSON, MO 65616-3462
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | No | No | Emergency light and bell not working | 9/18/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace the badly rusted and oxidized door sill angle and the door, door frame, sill , sill support, at the lower level and the sill , sill angle, and facia between LL and ! | 9/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace the burnt out lights in the machine room | 9/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean up the car top | 9/21/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean up the mess in the pit | 9/21/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean up the very dirty pit | 7/25/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | clean the dirty car top | 7/25/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Repack the leaking jack seal | 7/25/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Replace the emergency light battery | 6/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean up the oil and water from the pit floor. | 7/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cut off the all thread above the new car ceiling on the car top | 7/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the dirty car top. | 7/19/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the standing water from the pit. | 5/7/2026 |
| A17.1-2016 : Elevators | 10.15 - Response to smoke detectors | 8.6.8.15.17 | Yes | No | Move the existing smoke detector in the hoistway up to within 12 inches of the hoistway ceiling. | 5/22/2026 |
| A17.1-2016 : Elevators | 10.15 - Response to smoke detectors | 8.6.8.15.17 | Yes | No | Add an additional smoke detector in the recently enclosed area in front of the elevator creating a foyer at the lowest level of the elevator entrances. | 5/22/2026 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | Yes | No | Replace the missing braille plates at all the floors where they are missing. | 5/22/2026 |