Inspection
Inspection Details
Equipment ID
25572
25572
Inspection Date
4/27/2021
4/27/2021
Inspection Type
Initial Inspection
Initial Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Rodney Stevenson
Rodney Stevenson
Relief Valve Pressure
Slide
10"
10"
Governor Rope Pull
450/900
450/900
Door Closing Force
23F/29R
23F/29R
External ID
6ba7f225-df1e-4b0e-83ac-904c90210075
6ba7f225-df1e-4b0e-83ac-904c90210075
Location
Old Judge Building, LLC
710 N 2nd St, St. Louis, MO
Phone: (314) 260-9266
710 N 2nd St, St. Louis, MO
Phone: (314) 260-9266
Owner
Attn: Brian Minges
Advantes Group
701 N 1st St, St. Louis, MO 63102
Phone: (314) 260-9266
Advantes Group
701 N 1st St, St. Louis, MO 63102
Phone: (314) 260-9266
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 6/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational with 110v source removed. | 6/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Provide fire service Phase 2 instructions inside the car. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Clean the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be cleaned. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Install missing electrical box covers on the car top. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The hoist ropes shall have data tags installed. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | All electrical wires in the hoistway shall be enclosed in conduit or metal raceway, or be in compliance with NFPA 70. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 6/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car operating panel shall be secured. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways shall be fully enclosed and made of solid construction. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Unit shall have a code compliant code data plate. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Install missing duct covers and electrical box covers in the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The pit door shall be self-closing and self-locking. It is also recommended that a warning/danger sign be put on the pit door. | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase 2 fire service switch shall be two position type. Shall not have bypass feature operational. Unit Red Tagged. | 6/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire alarm initiating devices (smoke detectors) shall be provided and shall active Phase 1 fire service. Unit Red Tagged. | 6/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The fire service Phase 2 key switch shall be operational. Unit Red Tagged. | 6/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | All car top electrical boxes shall have covers installed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | "In Case of Fire" signage shall be installed at each landing. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 3/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational with 110v source removed. | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The building is in the process of adding smoke detectors to the elevator and testing will be required when complete. Elevator not red tagged. | 3/31/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Counterweight guards shall extend from a point not more than 12" above the pit floor to a point not less than 7' above the pit floor. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The walk-in pit door shall be self-closing. | |
| A17.1-2016 : Elevators | 2.27 - Rope fastenings | 8.11.2.1.2(cc) | No | No | The car and counterweight retaining clips shall be spaced correctly. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A governor rope data tag shall be provided. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is expired. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. A maintenance check chart and wiring diagrams are the only items present. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Label the disconnect with the location, source, and breaker numbers of the panel from which it is fed. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. |