Inspection
Inspection Details
Equipment ID
5890
5890
Inspection Date
4/29/2021
4/29/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
13
13
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
debfe711-6741-4ab1-9cfa-c962c0bd1893
debfe711-6741-4ab1-9cfa-c962c0bd1893
Location
The Westin Hotel-St. Louis
811 Spruce St, St. Louis, MO
Phone: (314) 621-2000
811 Spruce St, St. Louis, MO
Phone: (314) 621-2000
Owner
Attn: The Westin St. Louis
HEI St. Louis LLC
811 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (314) 552-5810
Email: Tom.dietz@westinstlouishotel.com
HEI St. Louis LLC
811 SPRUCE ST, SAINT LOUIS, MO 63102
Phone: (314) 552-5810
Email: Tom.dietz@westinstlouishotel.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete. Need to test car and counterweight buffers, safeties, 125% brake test, and fire service. | 4/15/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/15/2021 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor does not work. | 4/15/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 4/29/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 6/2/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not work. Re-inspection required | 3/13/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 9/3/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required | 9/3/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 2/4/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 6/6/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two-way communication inoperable and shall be repaired, or replaced. | 7/29/2025 |