Inspection
Inspection Details
Equipment ID
17944
17944
Inspection Date
4/29/2021
4/29/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
4"
4"
Governor Rope Pull
250/460
250/460
Door Closing Force
18
18
External ID
16edbfc9-df91-4512-87e0-31ac7c01c9fe
16edbfc9-df91-4512-87e0-31ac7c01c9fe
Location
Chapel View
4249 MICHIGAN AVE, SAINT LOUIS, MO
Phone: (314) 352-7600
4249 MICHIGAN AVE, SAINT LOUIS, MO
Phone: (314) 352-7600
Owner
Attn: Leasing Office
Chapel View One
4249 Michigan Ave, St. Louis, MO 63111
Phone: (314) 352-7600
Email: manager@chapelviewapts.com
Chapel View One
4249 Michigan Ave, St. Louis, MO 63111
Phone: (314) 352-7600
Email: manager@chapelviewapts.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine room door must be self closing and locking. | 11/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Permanent electric lighting shall be provided in the machine room and shall be not less than 19 fc at the floor level. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | The code data plate required by A17.1 2005, Section 8.9, shall be provided in plain view, securely attached to each main line disconnect or controller. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.5 Counterweight Runby Data Plate | No | No | A counterweight runby data plate shall be provided in the pit. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.8.1 Electrical Equipment and Wiring | No | No | The machine room air conditioners must be permanently wired. Note: The extension cord attached to a light fixture hanging over the machine is not allowed. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Permanent electric lighting shall be provided in the machine room and shall be not less than 19 fc at the floor level. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.8.1 Electrical Equipment and Wiring | No | No | The machine room air conditioners must be permanently wired. Note: The extension cord attached to a light fixture hanging over the machine is not allowed. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | The new light added in the machine room does not work. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures are missing from the MCP. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Replace burnt out lights in machine room. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No State certificate in the machine room. | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove trash from pit. | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Top of car shall be cleaned. (oil all over top of car) | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Machine room ceiling leaks, it must be propely sealed to keep water and other debris out. |