Inspection
Inspection Details
Equipment ID
1160
1160
Inspection Date
5/7/2021
5/7/2021
Inspection Type
Special Inspection
Special Inspection
Inspector Name
Michael Terhune
Michael Terhune
Mechanic Name
Frank Berkey
Frank Berkey
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
66781eb9-8092-427b-a412-9a00a4d67b1b
66781eb9-8092-427b-a412-9a00a4d67b1b
Location
Truman Building
301 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 571-7830
301 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 571-7830
Owner
Attn: INTERAGENCY
State of Missouri- Truman Bldg-INTERAGENCY
301 W HIGH ST STE 730, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
State of Missouri- Truman Bldg-INTERAGENCY
301 W HIGH ST STE 730, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
Billing
Attn: INTERAGENCY
OA- FMDC-HST RM 730-INTERAGENCY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
OA- FMDC-HST RM 730-INTERAGENCY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Clean car top. | 1/31/2026 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit. | 1/31/2026 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Clean machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Shorten ropes, no runby present. | 2/22/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Provide door maintenance on all floors. Rollers, upthrust devices, gibs, etc. All items showing wear and in need of maintenance. | 2/22/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Provide monthly FFS testing log in machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide MCP in machine room. | 1/31/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Emergency power not tested at time of inspection. | 2/22/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide MCP in machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 1/31/2026 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Shorten main hoisting ropes, only 1" of runby in pit. | 1/10/2024 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 1/31/2026 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | Emergency power not tested at time of inspection. | 1/10/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Shorten ropes, no runby in pit. | 1/23/2025 |