Inspection
Inspection Details
Equipment ID
1161
1161
Inspection Date
5/7/2021
5/7/2021
Inspection Type
Special Inspection
Special Inspection
Inspector Name
Michael Terhune
Michael Terhune
Mechanic Name
Frank Berkey
Frank Berkey
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
66d00064-1db6-4902-af1d-e7de6d89a681
66d00064-1db6-4902-af1d-e7de6d89a681
Location
Truman Building
301 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 571-7830
301 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 571-7830
Owner
Attn: INTERAGENCY
State of Missouri- Truman Bldg-INTERAGENCY
301 W HIGH ST STE 730, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
State of Missouri- Truman Bldg-INTERAGENCY
301 W HIGH ST STE 730, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
Billing
Attn: INTERAGENCY
OA- FMDC-HST RM 730-INTERAGENCY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
OA- FMDC-HST RM 730-INTERAGENCY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoisting ropes rouged and undersized. | 1/25/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoist ropes rouged, replace. | 2/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Provide door maintenance on all landing doors, rollers, upthrust devices, etc. All components in need of maintenance. | 2/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | 1/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 1/31/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room. | 1/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room. | 1/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Provide monthly FFS testing log in machine room. | 1/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | Yes | No | Emergency power not tested at time of inspection. | 2/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP in machine room. | 1/31/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 1/31/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoist ropes rouged, replace. (d) | 3/1/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light not working. | 1/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 3/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working at time of inspection. | 1/10/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 1/31/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Emergency power not tested at time of inspection. | 1/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 9/11/2024 |