Inspection
Inspection Details
Equipment ID
5743
5743
Inspection Date
7/24/2018
7/24/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
F. Scott Gibson
F. Scott Gibson
Mechanic Name
Joseph Ammons
Joseph Ammons
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
fdd33c57-a1ee-4e51-8d5e-d19f4f1539d1
fdd33c57-a1ee-4e51-8d5e-d19f4f1539d1
Location
Burrell Center Inc.
3401 BERRYWOOD DR STE 204, COLUMBIA, MO
3401 BERRYWOOD DR STE 204, COLUMBIA, MO
Owner
Burrell Center Inc
3401 BERRYWOOD DR STE 204, COLUMBIA, MO 65201-6515
3401 BERRYWOOD DR STE 204, COLUMBIA, MO 65201-6515
Billing
Attn: Burrell Behavioral Health
3401 BERRYWOOD DR STE 204, COLUMBIA, MO 65201-6515
3401 BERRYWOOD DR STE 204, COLUMBIA, MO 65201-6515
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Articles or material not necessary for the operation of the elevator shall not be stored in the Elevator Machine Room. | 7/25/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not connect. | 4/14/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Fire caulk around conduit penetrations, replace damaged ceiling tiles in machine room. | 4/14/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 4/14/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Install outlet/switch covers. | 4/14/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | Yes | No | Fire caulk hoistway and pit fire penetrations. | 4/14/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | Yes | No | Sump cover to be relatively flush with floor. | 4/14/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit lighting shall not be less than 10fc. | 4/14/2025 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 3.18.3.3 | Yes | No | Jack/cylinder does not allow full compression of buffer springs before cylinder bottoms out in jack. | 4/14/2025 |
| A17.1-2016 : Elevators | 5.12 - Car Buffer | 3.6.3 | Yes | No | Buffer spring height does not allow for minimum overtravel of 3.75". | 4/14/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.1 Phase I Emergency Recall Operation After Device Actuation | Yes | Yes | 2nd and 3rd floor devices not permanently installed (ceilings not installed, devices hanging by their wiring). | 4/14/2025 |