Inspection
Inspection Details
Equipment ID
15028
15028
Inspection Date
5/13/2021
5/13/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Geff Noyes
Geff Noyes
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
26
26
External ID
d6ce6a12-a0ac-4804-b588-b6ab6395132b
d6ce6a12-a0ac-4804-b588-b6ab6395132b
Location
Iatan Power Plant
20250 STATE ROUTE 45 N, WESTON, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@kcpl.com
20250 STATE ROUTE 45 N, WESTON, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@kcpl.com
Owner
Attn: UNK
KC Power & Light
1201 WALNUT, KANSAS CITY, MO 64141
Phone: (000) 000-0000
Email: lynette.hurst@kcpl.com
KC Power & Light
1201 WALNUT, KANSAS CITY, MO 64141
Phone: (000) 000-0000
Email: lynette.hurst@kcpl.com
Billing
Attn: UNK
Iatan Power Plant
20250 STATE ROUTE 45 N, WESTON, MO 64098
Phone: (000) 000-0000
Email: acctspay@kcpl.com
Iatan Power Plant
20250 STATE ROUTE 45 N, WESTON, MO 64098
Phone: (000) 000-0000
Email: acctspay@kcpl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Rope gripper does not function. Need to provide means for ascending car and unintended motion protection. | 9/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure in machine room | 3/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 3/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 5/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | All elevators in the same building shall use the same key for firefighter operation | 5/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Fire hat jewel needs to be installed on firefighter cabinet panel | 5/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | All elevators in the same building shall have firefighter keyswitches operated by the same key | 5/25/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan in machine room | 1/1/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No up to date maintenance records in machine room | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate displayed | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | install fire hat jewel in firefighter operation panel. | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | car firefighter operation panel shall have a locked cover. | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone button on car operating panel does not activate emergency phone. | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | machine room air conditioner does not function. | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 1/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency light and bell | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the water from the pit | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase 2 fire service not working |