Inspection
Inspection Details
Equipment ID
16257
16257
Inspection Date
5/18/2021
5/18/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
26
26
External ID
fa117d68-b96f-424f-905a-22406bf5b4ae
fa117d68-b96f-424f-905a-22406bf5b4ae
Location
Lofts at 415
415 N 3RD ST, SAINT JOSEPH, MO
Phone: (816) 749-4663
415 N 3RD ST, SAINT JOSEPH, MO
Phone: (816) 749-4663
Owner
Attn: UNK
Mitchell Park Plaza Equities
55 5TH AVE FL 15, NEW YORK, NY 10003
Phone: (000) 000-0000
Mitchell Park Plaza Equities
55 5TH AVE FL 15, NEW YORK, NY 10003
Phone: (000) 000-0000
Billing
Attn: Jayne Simerly
Mitchell Park Plaza
1300 S 11TH ST STE 100, SAINT JOSEPH, MO 64503
Phone: (816) 749-4663
Email: mitchellparkmgr@tiehengroup.com
Mitchell Park Plaza
1300 S 11TH ST STE 100, SAINT JOSEPH, MO 64503
Phone: (816) 749-4663
Email: mitchellparkmgr@tiehengroup.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Provide tye ABC fire extinguisher inside control room near access door | 7/29/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 7/26/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | 8/24/2021 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Replace broken bezel identification marking for firefighter keyswitch | 8/24/2021 |
| A17.1-1996 : Elevators | 3.26 - Broken rope, chain, or tape switch | 1001.2(c)(9) | Yes | No | Slack belt switch does not function. | 8/13/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | 8/24/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace missing car direction lantern fixture in car enclosure opening. | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No MCP | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(5) | No | No | Written procedures for tests and inspections need to be kept in the control room. | 9/12/2024 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.19.2 | Yes | Yes | Perform annual no load safety test | 8/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 9/12/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 9/12/2024 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace missing car direction lantern fixture in the car enclosure | 9/12/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit access door needs to be self-locking | 9/12/2024 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | No | No | Install heat detector within 24 inches from each machine room sprinkler | 9/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 8/22/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions next to hall firefighter keyswitch | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(5) | No | No | Keep written procedures for tests and inspections on site | 9/12/2024 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Perform unintended motion and ascending car protection tests | 8/22/2023 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Perform full load safety test | 8/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in the control space. | 9/12/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 7/2/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | DOOR CLOSE BUTTON IS LABELED #1 | 9/12/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.1a | No | No | HOLE IN MACHINE ROOM CELING NEEDS TO BE PATCHED AND FIRE RATED | 9/12/2024 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | CAR DOOR GAP IS >1/2" . NEEDS TO BE ADJUSTED | 9/12/2024 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.6 | No | No | DOOR GAP IS >1/2'' | 6/27/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | SUPPLY WORKING LIGHT AND BELL | 4/29/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE WORKING PHONE |