Inspection
Inspection Details
Equipment ID
14089
14089
Inspection Date
5/12/2021
5/12/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
16e0c2e6-7d4a-47f8-9bf5-bef3b17cee0f
16e0c2e6-7d4a-47f8-9bf5-bef3b17cee0f
Location
Homer Phillips
2601 WHITTIER ST, SAINT LOUIS, MO
Phone: (314) 535-3223
2601 WHITTIER ST, SAINT LOUIS, MO
Phone: (314) 535-3223
Owner
Attn: EPV Dignity House LLC
EPV Dignity House LLC
125 John Roberts Rd #12, South Portland, ME 04106
Phone: (616) 340-3753
EPV Dignity House LLC
125 John Roberts Rd #12, South Portland, ME 04106
Phone: (616) 340-3753
Billing
Attn: Jill Richards, Regional Manager
Homer Philliips Dignity House II
2601 Whittier St, St. Louis, MO 63113
Phone: (207) 780-8050
Alt Phone: (314) 309-6975
Email: jrichards@eaglepointco.com
Homer Philliips Dignity House II
2601 Whittier St, St. Louis, MO 63113
Phone: (207) 780-8050
Alt Phone: (314) 309-6975
Email: jrichards@eaglepointco.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Maintain machine room lighting three out of four bulbs out | 2/13/2020 | ||
conversion | conversion | n/a | Pit light inopeartive | 2/13/2020 | ||
A17.1-1996 : Elevators | 2.15 - Static control | 1001.2(b)(13) | x | Elevator failed static 125% test. Brake did not hold. Elevator red-tagged. | 10/29/2018 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/13/2020 | ||
A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) - no reinspect | Worm gear is leaking excessively on car top and in the cab. | 2/13/2020 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x | Water in the pit. | 5/13/2020 | |
A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) - no reinspect | Worm shaft seal on drive machine worn and leaking. Repair/replace as needed. | 2/11/2021 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 2/25/2021 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate. | 2/11/2021 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide on-site maintenance control program. | 11/15/2021 | ||
A17.1-1996 : Elevators | 2.18 - Traction drive machines | 1001.2(b)(16) | x | Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed. | 11/15/2021 | |
A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | Clean oil from car top, fan and ceiling/fixtures. | 11/15/2021 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean pit. | 11/15/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Sheave seal worn and leaking, repair as needed. Clean up oil. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Hoistway door closer is missing retainer clip for rod, replace. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Smoke detector in pit has been removed, determine cause. Replace. | ||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Heat detector head in pit has been removed. Determine cause, replace. |