Inspection
Inspection Details
Equipment ID
10702
10702
Inspection Date
5/25/2021
5/25/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
353bb039-bf6c-4607-b24d-084e5fa9b776
353bb039-bf6c-4607-b24d-084e5fa9b776
Location
Parkview Elderly Apts
4451 Forest Park Ave, St. Louis, MO
Phone: (314) 533-3350
4451 Forest Park Ave, St. Louis, MO
Phone: (314) 533-3350
Owner
Attn: Parkview Elderly Apts
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 533-3350
Email: areeves@habitat.com
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (314) 533-3350
Email: areeves@habitat.com
Billing
Attn: Andy Reeves
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: areeves@habitat.com
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: areeves@habitat.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency bell does not work | 2/7/2019 |
| conversion | conversion | n/a | No | No | Pits shall be clean | 5/9/2019 |
| MO Minimum : Elevators | (E) - Machines | (E)1 | No | No | Repair or replace machine drive sheave. | 5/9/2019 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Replace contaminated machine brake shoes. | 2/27/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Car door restrictor does not work. | 5/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work on battery back-up. | 5/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site for each elevator. | 6/7/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program not on site | 6/7/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pits shall be kept dry, clean & free of equipment or material not relating to the operation of the elevator | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A MCP shall be kept for each unit and kept on site | 3/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Rear car door restrictor does not work. Repair | 1/5/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has trash and debris in it. Clean elevator pit | 3/27/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Top of hoistway smoke needs to be programmed correctly to go to primary floor. | 10/18/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Only one smoke detector in the shared machine room for all three elevators. Provide additional smoke detectors to achieve proper coverage. | 10/18/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | All three elevators will have emergency generator power. Emergency power shall be tested once modernizations are complete. | 10/18/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Provide additional relay to separate the shunt trip function between the 2 hoistways. Shunt to only activate when heat detector in the respective hoistway is triggered. | 10/18/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Phone monitoring will be added to duplex lobby. When all three are completed, push button station must be checked. | 10/18/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | All three elevators will have emergency generator power. Emergency power shall be tested once modernizations are complete. | 5/27/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Phone monitoring will be added to duplex lobby. When all three are completed, push button station must be checked. | 5/27/2025 |