Inspection
Inspection Details
Equipment ID
25453
25453
Inspection Date
5/17/2021
5/17/2021
Inspection Type
Initial Inspection
Initial Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Andrew Smith
Andrew Smith
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
9524701c-4040-49fe-a5c8-f6783155789d
9524701c-4040-49fe-a5c8-f6783155789d
Location
Columbia Mennonite Guest House
4409 St. Charles Rd, Columbia, MO
Phone: (620) 664-4123
4409 St. Charles Rd, Columbia, MO
Phone: (620) 664-4123
Owner
Attn: Columbia Mennonite Guest House
Columbia Mennonite Guest House
4409 St. Charles Rd, Columbia, MO 65201
Phone: (620) 664-4123
Columbia Mennonite Guest House
4409 St. Charles Rd, Columbia, MO 65201
Phone: (620) 664-4123
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.4 | No | No | Provide electric/mechanical interlock for upper landing gate. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.4 | No | No | Provide electrical/mechanical interlock for lower landing door. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.6 | No | No | Running clearance between sill @ rear entrance under .375 inch minimum. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.7 | No | No | Clearance between platform guardrail and wall is 5 1/2". The tolerance is no less than 2", no more than 3". | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.1 | No | No | Provide solid enclosure of hoistway for entirety of hoistway. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.6 - Platforms | 2.6.3 | No | No | Enclosure walls shall not deform more than one inch. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.11 - Emergency Signals | 2.11.1 | Yes | No | Provide audible alarm upon activation of emergency stop switch. | 10/18/2021 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.6 - Platforms | 2.6.6.3 Auxiliary Lighting (Re-Inspection) | No | No | Provide emergency overhead lighting in hoistway. | 7/18/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.7 - Capacity, Speed, and Travel | 2.7.2 | No | No | Provide capacity plates with operating instructions at each landing. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.10 - Operating Devices and Control Equipment | 2.10.1 | Yes | No | Provide call/send stations at each landing @ maximum height of 48" from the landing floor. | 10/18/2021 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.7 | No | No | Provide fused, lockable main line disconnect for lift power within sight of lift. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.2.2 | No | No | Top landing gate and surrounding walls shall be a minimum of 42" tall from landing floor. | 9/30/2024 |
| ICC A117.1-2009 | 410.2 - Lift Entry | 410.2.1 | No | No | Provide low energy power operators at each landing door/gate. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | State Operating Certificate not available. Present site contact person has changed, however the Email address is correct. | 10/21/2025 |
| ASME A18.1-2005 : Lifts & Chairlifts | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Initial Violations have been corrected. Operating Certificate not available! | 10/21/2025 |