Inspection
Inspection Details
Equipment ID
2829
2829
Inspection Date
5/28/2021
5/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jeffrey Borgeson
Jeffrey Borgeson
Relief Valve Pressure
820
820
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
ef6521d1-b4d9-4d9e-8d12-70ab164c19af
ef6521d1-b4d9-4d9e-8d12-70ab164c19af
Location
Maryville Treatment Center
30277 US HIGHWAY 136, MARYVILLE, MO
Phone: (660) 582-6542
30277 US HIGHWAY 136, MARYVILLE, MO
Phone: (660) 582-6542
Owner
Attn: Maryville Treatment Center-INTERAGENCY
Maryville Treatment Center-INTERAGENCY
30277 US Hwy 136, Maryville, MO 64468
Phone: (000) 000-0000
Email: Tiffany.Chambers@doc.mo.gov
Maryville Treatment Center-INTERAGENCY
30277 US Hwy 136, Maryville, MO 64468
Phone: (000) 000-0000
Email: Tiffany.Chambers@doc.mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-closing | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 7/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No maintenance control plan on site | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No hard copy maintenance records on site | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform safety test | 7/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Perform overspeed valve test on or before next inspection | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(c) On-Site Documentation (Written Checkout Procedures) | No | No | Written checkout procedure for overspeed valve test needs to be kept in the machine room | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform pressure relief test | 7/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Distance between swing hoistway door and edge of landing sill exceeds .75 inches at the bottom and third landings. A17.1 1996 rule 110.4 | 7/18/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-closing. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(c) On-Site Documentation (Written Checkout Procedures) | No | No | Written checkout procedure for overspeed valve needs to be kept in the machine room. | 9/22/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Install periodic test tag for pressure relief test | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | Yes | Distance between hoistway swing door and the edge of the landing sill exceeds .75 inches at all landings (second notice). A17.1 1996 rule 2500.11 | 12/4/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | IN CAR EMERGENCY PHONE NOT WORKING | 7/30/2025 |