Inspection
Inspection Details
Equipment ID
17360
17360
Inspection Date
8/3/2017
8/3/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
Location
Argosy Casino
777 NW Argosy Pkwy, Riverside, MO
Phone: (816) 746-3588
777 NW Argosy Pkwy, Riverside, MO
Phone: (816) 746-3588
Owner
Argosy Casino
777 NW Argosy Pkwy, Riverside, MO 64150
777 NW Argosy Pkwy, Riverside, MO 64150
Billing
Attn: Argosy Casino
777 NW Argosy Pkwy, , MO 64150
777 NW Argosy Pkwy, , MO 64150
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | replace phase 1 keyswitch collar, can no longer read the woords on, off, bypass, or fire service | 11/23/2025 |
| conversion | conversion | n/a | No | No | landing 2 is missing the upthrust roller on the leading edge of the hoistway door on the fast panel | 11/23/2025 |
| conversion | conversion | n/a | No | No | governor tail sheave switch arm is not between the pins on the tail sheave | 11/23/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | replace machine room light bulbs, they are burnt out | 11/23/2025 |
| A17.1-1996 : Elevators | 3.26 - Broken rope, chain, or tape switch | 210.2(f) | Yes | No | belt monitor is flashing error on center belt, monitor has been bypassed alowing car to run, belts are rouged. Repair the belt monitor, remove the bypass, and clean the rouge off of the belts | 10/20/2020 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | No | No | the hoist belt monitor is flashing an error that 2 of the belts are failing. Check the belts and if they test good repair the monitor, if the belts test bad replace the hoist belts | 3/30/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | a monthly fire service test log is to be posted in the machine room and filled out monthly | 11/23/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is to be updated every year with the current certificate | 11/23/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | the door open button did not work on fire service phase 2. did not red tag this elevator because both of the elevators that service the parking garage failed for the same reason | 3/30/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | machine room light bulbs were all burnt out, replace/repair machine room lights | 11/23/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | none of the machine room lights are working, repair or replace light fixtures | 11/23/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | repair cab ceiling lights, two of the fixtures are not working | 11/23/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Keep pit free of dust and debris | 11/23/2025 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | No | No | Missing upthrust at 2nd floor door | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Repair/Re-Lamp in car lighting | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Owner to keep updated monthly fire service records | |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.3.9 | Yes | No | Repair/replace remote governor reset solenoid - 2.7.6.5: means necessary for testing | 9/4/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Missing Phase 1 Instructions at main egress fixture | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.1.6.5 Fire Extinguishers | No | No | Provide updated fire extinguisher | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Clean debris from the pit / Clean car top. Repeat violation 9/4/2025 | |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | 2nd landing fast hoistway door missing one of the up thrust rollers; Repeat violation 8/26/2024. Repeat violation 9/4/2025 | |
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 102 | No | No | Repair flex on car top that is broken on both ends for cab fan | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Update expired fire extinguisher inspection tag from 2022. Repeat violation 9/4/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Update PM log / Owner to keep updated monthly Fire recall log updated. Repeat violation 9/4/2025 |