Inspection
Inspection Details
Equipment ID
23428
23428
Inspection Date
5/27/2021
5/27/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Joseph Wuelling
Joseph Wuelling
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15
15
External ID
65edd79b-8eab-46e6-95e7-ffd80b108c50
65edd79b-8eab-46e6-95e7-ffd80b108c50
Location
4534 Olive LLC
4534 Olive St, St. Louis, MO
Phone: (314) 361-7117
4534 Olive St, St. Louis, MO
Phone: (314) 361-7117
Owner
Attn: 4534 Olive LLC
4534 Olive LLC
393 N Euclid Ave, St. Louis, MO 63108
Phone: (314) 361-7117
4534 Olive LLC
393 N Euclid Ave, St. Louis, MO 63108
Phone: (314) 361-7117
Billing
Attn: Rothschild Management LLC
Rothschild Management LLC
393 N Euclid Ave, St. Louis, MO 63108
Phone: (314) 361-7117
Email: commercial@rothschidstl.com
Rothschild Management LLC
393 N Euclid Ave, St. Louis, MO 63108
Phone: (314) 361-7117
Email: commercial@rothschidstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide up to date test tag on fire extinguisher. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on site maintenance records and monthly elevator fire log. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Existing battery back up system does not work. | 6/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide fire extinguisher and test it annually. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | No | Brake does not hold 125% capacity. Re-inspection required | 7/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Reprogram the emergency phone to call a monitored station | 4/24/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Repair inoperative emergency light | 4/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | Emergency rescue unit does not work, battery has no power, Re-inspection required | 10/3/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Overhead machine space lighting does not work and is not mounted properly, needs repaired. Re-inspection required | 10/3/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Overhead machine space lighting does not work and is not mounted properly, needs repaired. Re-inspection required | 4/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Top of hoistway lights are not working, repair as needed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | All hoistway doors are missing bottom door fire tabs, provide. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. |