Inspection
Inspection Details
Equipment ID
11691
11691
Inspection Date
5/18/2021
5/18/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
47385854-1f9f-4af2-9290-979e77ceed74
47385854-1f9f-4af2-9290-979e77ceed74
Location
West Park II
12647 OLIVE BLVD, SAINT LOUIS, MO
Phone: (314) 727-6664
12647 OLIVE BLVD, SAINT LOUIS, MO
Phone: (314) 727-6664
Owner
Attn: Mary Lou Willbrand, Property Manager
West Park II Investors, LLC c/o Larson Commercial Real Estate
14567 N Outer 40, Ste 350, Chesterfield, MO 63017
Phone: (314) 787-7429
Alt Phone: (314) 787-5392
Email: marylou.willbrand@larson-commercial.com
West Park II Investors, LLC c/o Larson Commercial Real Estate
14567 N Outer 40, Ste 350, Chesterfield, MO 63017
Phone: (314) 787-7429
Alt Phone: (314) 787-5392
Email: marylou.willbrand@larson-commercial.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Car door restrictor does not work. | 5/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 5/8/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 8/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 8/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | 10/12/2023 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Non-elevator related items shall not be stored in the machine room. (HVAC materials, refrigerant, etc.) | 12/5/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | No | No | Machine room lighting shall be repaired. One or more bulbs are not working. | 12/5/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be properly documented. | 12/5/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.7.2 Seizing of Rope Ends | No | No | Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper. | 12/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Counterweight runby signage needs to be updated with proper maximum allowable measurement. Currently states 22", at which the overhead deflector sheave would crush cartop handrail. | 12/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | 2.4.7.2 - Cartop refuge space needs to be properly marked to allow for 43" of refuge after counterweight full compression and car bounce calculations. | 12/5/2024 |