Inspection
Inspection Details
Equipment ID
13169
13169
Inspection Date
7/27/2018
7/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
650
650
Slide
Governor Rope Pull
Door Closing Force
27F 28R
27F 28R
External ID
a953215c-0f33-4659-b29b-6904536a9041
a953215c-0f33-4659-b29b-6904536a9041
Location
McDonald High School
100 MUSTANG DR, ANDERSON, MO
100 MUSTANG DR, ANDERSON, MO
Owner
McDonald Co R-1 Schools
100 MUSTANG DR, ANDERSON, MO 64831-7305
100 MUSTANG DR, ANDERSON, MO 64831-7305
Billing
Attn: McDonald Co R-1 Schools
10 STAMPEDE DR, ANDERSON, MO 64831-7801
10 STAMPEDE DR, ANDERSON, MO 64831-7801
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Obtain and display a current state operating certificate in the machine room. | 9/6/2019 |
| conversion | conversion | n/a | No | No | Have the fire extinguisher re-certified. | 9/6/2019 |
| conversion | conversion | n/a | No | No | repair the emergency phone as there is no dial tone on the line. | 9/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as the incomming line is dead no dial tone. | 2/11/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as it will not dial out. | 1/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | No | No | Replace all the broken floor tile in the car to elemonate the trip hazard and protect the sub floor. | 8/21/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 8/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | obtain and display a current state operating certificate in the machine room | 12/7/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as the incoming line is dead. | 7/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as it will not dial out. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a currebnt state operating certificate in the machine room |