Inspection
Inspection Details
Equipment ID
14889
14889
Inspection Date
5/20/2021
5/20/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
TBD
TBD
Governor Rope Pull
TBD
TBD
Door Closing Force
18
18
External ID
4ad7627d-5a6d-4ba6-ad93-a866c17a11f6
4ad7627d-5a6d-4ba6-ad93-a866c17a11f6
Location
City View Apts-Bldg 30
110 N 17th St, Bldg 30, St. Louis, MO
Phone: (314) 588-1177
110 N 17th St, Bldg 30, St. Louis, MO
Phone: (314) 588-1177
Owner
Attn: Mills Properties Inc Cityview Apartments
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | No | No | 2.18.5.3 - A governor rope data tag shall be installed. | 5/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | 2.20.2.2 - A suspension rope data tag shall be installed. | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/15/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | The hoist ropes are bad and shall be replaced ASAP. Unit Red Tagged until ropes can be replaced. | 5/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/17/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The hoist ropes shall have data tags installed. | 6/17/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Did not finish the category 5 portion of the test. Only category 1 items were able to be completed. A category 5 test shall be completed. | 5/25/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Did not finish the category 5 portion of the test. Only category 1 items were able to be completed. A category 5 test shall be completed. | 6/11/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall operate per code. Phone dials, but no one answers. | 1/17/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | 8/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency phone is not working. Elevator Red Tagged. | 9/12/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door lock is broken and must be repaired to prevent access to machine room by unauthorized persons. Access doors shall be self-closing and self-locking. | 1/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A permanent and unobstructed means of access shall be provided to machine room (debris and non-elevator related materials impeding access to ladder to machine room). | 1/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Counterweight buffer is being compressed more than 25% when car is at top terminal floor; ropes must be shortened to provide code compliant runby. | 1/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete - All weight prtions of the 5 year test shall be completed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car got stuck in the overhead when the safeties were set. |