Inspection
Inspection Details
Equipment ID
17924
17924
Inspection Date
7/27/2018
7/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Richard Dalman
Richard Dalman
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
10
10
External ID
00266ccb-8d38-4d53-b4d7-96c0aab6b828
00266ccb-8d38-4d53-b4d7-96c0aab6b828
Location
Argosy Casino Hotel
777 NW ARGOSY PKWY, RIVERSIDE, MO
777 NW ARGOSY PKWY, RIVERSIDE, MO
Owner
Argosy Casino
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
Billing
Attn: Argosy Casino
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | both of the kellum grips that hold the traveling cables have broken and need replaced | 11/23/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually | 11/23/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | monthly fire service test log in the machine room has not been filled out monthly, test fire service monthly and fill out the log in the machine room | 11/23/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | machine room maintenance logs have not been filled out since 2017, fill out maintenance log for every callback and maintenance visit | 11/23/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state of Missouri annually | 11/23/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | monthly fire service test log has not been filled out monthly, test fire service monthly and fill out log in the machine room | 11/23/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | replace burnt out machine room lights, all of the lights are not working in the machine room | 11/23/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Remove old permit with updated one in a displayable location | 11/23/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Owner to keep monthly fire service log updated | 11/23/2025 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.19.3 | Yes | No | Repair remote governor reset - 2.7.6.5 provide means for testing | 11/23/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Keep pits free of dust and debris | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Provide proper counterweight runby - remove stinger | 9/2/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone is functioning however due to static the operator has difficulty hearing | 9/2/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually, repeat 9/2/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Monthly fire service test log has not been filled out monthly, test fire service monthly and fill out log in the machine room; repeat violation 8/26/2024, repeat 9/2/2025 and update PM logs | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone speaker - security cannot hear occupant, repeat 9/2/2025 reinspection required within 15 days | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean debris from the pit |