Inspection
Inspection Details
Equipment ID
7448
7448
Inspection Date
4/30/2021
4/30/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Jeffrey Borgeson
Jeffrey Borgeson
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
12
12
External ID
33aab693-61ca-4958-bdcd-0b46c0414d4d
33aab693-61ca-4958-bdcd-0b46c0414d4d
Location
Holiday Inn Express
1995 MACON ST, N KANSAS CITY, MO
Phone: (816) 218-1100
1995 MACON ST, N KANSAS CITY, MO
Phone: (816) 218-1100
Owner
Holiday Inn Express
1425 S 5TH ST, SAINT CHARLES, MO 63301-2435
1425 S 5TH ST, SAINT CHARLES, MO 63301-2435
Billing
Attn: Holiday Inn Express
1995 MACON ST, N KANSAS CITY, MO 64116-3748
1995 MACON ST, N KANSAS CITY, MO 64116-3748
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 5/18/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 5/18/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | firefighters phase 2 instructions are hard to read, replace sign so the instructions can be read. | 5/18/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Maintenance Control Program (MCP) documents are not in the machine room | 1/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not being filled out monthly | 1/29/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit needs to be swept out, trash in pit | 1/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The tag on the machine room fire extinguisher is from 2020, the fire extinguisher is to be inspected and tagged annually | 1/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is to be kept in the machine room | 1/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | maintenance log book if from 2021, need lob book for 2023 | 1/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | need to have maintenance control program documents in the machine room | 1/29/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Do not store non elevator related items in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Cross at data tag is missing, provide crosshead data tag (207.3a) |