Inspection
Inspection Details
Equipment ID
4144
4144
Inspection Date
6/4/2021
6/4/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Relief Valve Pressure
435
435
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
b6420daa-b07c-4201-8485-8905d263638c
b6420daa-b07c-4201-8485-8905d263638c
Location
Doctors Pavillion
1115 ALASKA ST, WEST PLAINS, MO
Phone: (417) 256-9111
1115 ALASKA ST, WEST PLAINS, MO
Phone: (417) 256-9111
Owner
Attn: Ozark Medical Center
Ozark Medical Center
PO Box 1100, WEST PLAINS, MO 65775
Phone: (417) 256-9111 Ext: 6200
Email: trena.parker@ozarksmedicalcenter.com
Ozark Medical Center
PO Box 1100, WEST PLAINS, MO 65775
Phone: (417) 256-9111 Ext: 6200
Email: trena.parker@ozarksmedicalcenter.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Must Provide all required MCP and all on site documentation | 11/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | Must make Emergency alarm bell operable | 2/17/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Observation showed no current operating certificate on display. | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Observation showed no on-site documentation accessible for review. No oil usage logs, no maintenance records and no call back logs. | 11/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Observation showed the 110V disconnect is non-lockable. | 11/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Observation showed the alarm bell failed to operate. | 3/15/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell failed to operate | 3/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency bell failed | 2/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No records | 11/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell failed- Phone ok | 10/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No records | 11/16/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency Alarm operable. 1.6 | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Must make emergency light operable. 8.6.4.15 |