Inspection
Inspection Details
Equipment ID
17707
17707
Inspection Date
6/2/2021
6/2/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
dcfc64f0-ab63-480f-848f-7d79e06eb023
dcfc64f0-ab63-480f-848f-7d79e06eb023
Location
Horizon North Housing
5046 PAGE BLVD, SAINT LOUIS, MO
5046 PAGE BLVD, SAINT LOUIS, MO
Owner
Attn: Corrie Petschonek
Horizon North Housing
3001 Arsenal St, St. Louis, MO 63118
Phone: (000) 000-0000
Email: CPetschonek@hhstl.org
Horizon North Housing
3001 Arsenal St, St. Louis, MO 63118
Phone: (000) 000-0000
Email: CPetschonek@hhstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit, sump pump is full and not working. | 10/21/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Handrail in car is missing. Replace | 10/21/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV in pit not sealed. Test, tag and seal upon completion. | 4/15/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit. | 8/26/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Handrail in car is missing. Replace. | 8/26/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Sump pump may not be working. Hole is filled with liquid. Repair. | 8/26/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Phase II operations are worn and not legible. Replace. | 8/26/2021 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Cylinder packing worn and leaking, repair as needed. | 8/26/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean the pit(fluids). | 10/3/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Sump hole is filled with liquid (s), remove. | 10/3/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Determine if the sump pump is working correctly, if not then replace. | 10/3/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone is not working correctly, low voltage. | 10/2/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Unable to communicate with emergency personnel over phone, phone dials out, no answered. Re-inspection required |